The
universal digital metering system of the series AC-UNI,
available in sizes 96*96 and 144 * 144, will used to measure
the present values of a connected net. Following values will
be acquired and calculated:
-
Currents L1, L2, L3
-
Voltages
L1-N,L2-N, L3-N,L1-L2,
L2-L3,L3-L1
-
Frequency
-
Cos j
-
kW, kVAr, KVA
-
±kWh,
±kVAr
The current measurement will be done directly or for large
current values with a current transformer (.../5A or .../1A)
and the voltage measurement will be done directly or for large
voltage values with a voltage transformer (.../110V). |
| Input
Signals: |
1A-5A
direct, CT .../1A or .../5A
240V L-N direct, VT .../100V or .../110V |
| Accuracy: |
Class
1,5 |
| Burden: |
7
VA |
| Voltage
Insulation: |
2kV/1
min. at 50Hz |
| Terminals: |
for
wire till 2,5mm2 |
| Overload: |
Continuous:
1,2 IN/ UN
1s:
2 IN/
UN |
| Com-Port: |
RS-485 |
| Maintenance: |
none |
| Enviroment
Temperature: |
-20°
C till +50' C° 85 % rel. humidity |
| Installtion: |
as
desired |
| Common
Regulations: |
EN
50 178 |
| Radio
Disturbation: |
EN
55 022/B |
| EMC
according: |
EN
61 000 and EN V 50 140 |
| CE
proof: |
yes |
| Case
regulation |
DIN
EN 43700/43718 |
| Case
material: |
self
extinguishing plastic accor. UL 94 |
| Protection
degree: |
IP52 |
| Size: |
depending
on type |
| Weight: |
ca.
0,6 kg |
|